Fxo Interlinked Smoke Alarm by FIREXO

fxo Interlinked Smoke Alarm by FIREXO S.R.L., Foro Buonaparte, 12, 20121 Milano, Italy.

Model No: fxoIS1

*Life expectancy can vary due to environmental factors and care

Included with each Smoke Alarm; 

Contents; 

  1. Quick Set Up Mode + Function Description 
  2. Important Safety Information 
  3. Where to Install your Interlinked Smoke Alarm 
  4. Locations to Avoid 
  5. How to Install your Interlinked Smoke Alarm  
  6. Testing your Interlinked Smoke Alarm  
  7. Maintenance and Cleaning 
  8. Fire Safety Best Practice
  9. What to do in the Event of Fire
  10. Trouble Shooting 
  11. Limitations of Smoke Alarms
  12. Limited Warranty 

 

  1. Quick Set Up Mode + Function Description 

Quick Set Up Mode; this interlinked smoke alarm is part of fxos Interlinked Radio Emergency Fire Alarm System Technology (FIREFAST) but it can also be used as a stand-alone device.

If the smoke alarm is to be used as a stand-alone device i.e. it WILL NOT be connected via radio frequency to any other smoke, heat and/or CO devices then please see Section 5; How to Install your Interlinked Smoke Alarm. 

If this Interlinked Smoke Alarm WILL BE connected via radio frequency to any other smoke, heat or CO alarm as part of the FIREFAST system then please follow the pairing instructions below;

Lay out ALL fxo devices to be connected to each other via radio frequency, ensuing ALL devices have been turned on, activated and place approx. 15cm apart from each other on a flat surface. 

Select any Interlinked Smoke, Heat or CO alarm and pick any device to be the MASTER device. 

On the MASTER device, press the TEST button until the LED flashes green 3 times and release the TEST button and the LED will flash red;

On the 1st SLAVE device to be added to the MASTER; press the TEST button until the LED flashes green 2 times and release the TEST button and the LED will flash red on the SLAVE device and emit a short beep.   

Additional SLAVE devices can be added as per the above instructions until all SLAVE devices have been added. 

When all SLAVE devices have been added to the MASTER, the MASTER TEST button can be pressed once to END the pairing process and the red LED light will stop flashing. All smoke, heat and CO alarms have now been paired successfully and all interlinked via radio frequency. 

You have successfully paired the fxos Interlinked Radio Emergency Fire Alarm System Technology (FIREFAST) home fire safety protection system.

LED Light Sequence  LED Light Sequence Description 
1 LED green flash Approximately every 50-55 seconds to indicate normal operation 
2 LED green flashes Pairing Mode on SLAVE device
3 LED green flashes  Pairing Mode on MASTER device 
4 LED green flashes  Clear all paired data on MASTER or SLAVE device
Continuous LED red flashes  MASTER device is waiting on devices to be paired with it 
1 LED red flash  Approximately every 8 seconds with audible beep to indicate alarm fault condition
1 LED red flash  Approximately every 50-55 seconds with audible beep to indicate low battery condition 
3 LED red flashes  SLAVE device has successfully paired or unpaired to MASTER device 

Please ensure ALL devices have been successfully paired by pressing the TEST button on any one device and listening for an audible alarm on all paired devices activating. Please note; it can take 10-15 seconds for all paired devices to sound AND silence once a single device has been activated. 

It is recommended that each device is placed in the approximate location they are to be installed to ensure they will work BEFORE installing them to the ceiling.

 

1. Function Description

Test Mode; press and hold the TEST button and the audible alarm will sound and the LED warning light will flash. 

Alarm Mode; In the event of smoke being detected the audible alarm and LED warning light will flash until the audible alarm is silenced. 

Silence Mode; if the smoke alarm is in alarm mode, to silence the alarm, press the TEST button and this will silence the audible alarm for approx. 9 minutes (during this period smoke will not be detected). After 9 minutes it will revert to normal standby mode and begin to detect smoke again. 

Low Battery Condition; if low voltage is detected, a short audible beep will sound and the LED will flash every 50 seconds. 

Normal Operation; the LED will flash every 50 seconds.

 

2.Important Safety Information 

WARNING; PLEASE READ AND SAVE THESE INSTRUCTIONS 

DO NOT remove or disconnect the battery to silence unwanted alarms. Open windows to vent the room if needed.

DO NOT attempt to remove or replace the battery. Any attempt to do so may lead to malfunction of the alarm and invalidate any warranty. 

The TEST button is used to test the smoke alarm function – DO NOT use any other test method. 

This smoke alarm is not designed for commercial buildings and applications however, where deemed appropriate by a fire safety professional, may be used as supplemental protection. 

Smoke alarms alert household users in the vicinity of the smoke alarm that a possible fire condition has been detected. Hearing impairments, background noise, drugs, alcohol use etc could ensure persons may not hear the alarm. In this event, special consideration can be given to vibration alarms, and audio-visual devices to alert such persons. 

Smoke alarms have various restrictions on their use and DO NOT detect heat, flames or gas. There are various smoke detector applications for various types of fire or fire risk that is identified in the home. This device is a photoelectric smoke alarm and is designed to detect slow burning, smouldering fire types commonly found in the home. 

All smoke alarms must be tested weekly and replaced every 10 years.

 

3.Where to Install your Interlinked Smoke Alarm 

For full property protection, consideration should be given to fxos Interlinked Radio Emergency Fire Alarm System Technology (FIREFAST) and smoke alarms can be fitted in all bedrooms, living areas and circulation spaces (including landings and hallways on each level/storey), heat alarms in all kitchens, laundry rooms and garages and CO alarms in every room with a carbon fuelled appliance.

For reduced property protection, consideration should be given to fxos Interlinked Radio Emergency Fire Alarm System Technology (FIREFAST) and smoke alarms can be fitted in all main living areas and circulation spaces (including landings and hallways on each level/storey), heat detector in each kitchen and CO alarms in every room with a carbon fuelled appliance. 

As a minimum, smoke alarms should be located on every level in the home and in rooms where ignition sources are present and where the risk of fire is high such as in living areas and/or in the circulation spaces in close proximity to these rooms and areas i.e. hallways and landings. 

Smoke alarms should never be installed in kitchens, boiler rooms, laundry rooms etc. or any other room or area where dust, steam, insects etc could be present as this could lead to unwanted false alarms. For such areas, the user may consider installing heat alarms. 

Generally, for smoke alarms, the best location will be in the centre of the ceiling in any room or area ensuring the smoke alarm is at least 300mm away from any wall or obstruction. 

If it is necessary to install the smoke alarm on a wall, ensure it is installed 300mm from the ceiling and wall join/corner. Installing smoke alarms on the wall may lead to slower activation times compared to ceiling mounting the smoke alarm. This area, where the ceiling and walls meet is referred to as ‘dead air’ and if the smoke alarm is fitted within 150mm – 300mm of this point there may be a delay in the smoke alarm activating and early warning may not be provided. 

In rooms with simple sloped or peaked ceilings, smoke alarms should be installed 900mm (3ft) away from the highest point of the ceiling. 


 

4.Locations to Avoid 

DO NOT locate smoke alarms; 

In turbulent/moving air beside fans, heaters, air con units, windows etc that could delay the smoke alarm working. 

In areas of high humidity like bathrooms, shower rooms and where the temperature is likely to exceed 39°C or fall below 5°C. High humidity can lead to unwanted false alarms.

At the peak of an ‘A’ frame ceiling. 

Less than 300mm from a wall or other decorative ceiling mounted object when ceiling mounted. 

Where insects are present. 

In kitchens, boiler rooms, laundry rooms etc.  

In locations that would make maintenance and user testing dangerous i.e. directly over a top stair, void etc. 

On poorly insulated walls or ceilings.

 

5.How to Install your Interlinked Smoke Alarm  

Ensure the smoke alarm is activated by turning the setting to the ‘ON’ position as below. 

 

Press the TEST button to check it is functioning correctly BEFORE installation. 

Complete the section on the alarm nameplate with the Date of Installation. 

Mount the alarm base to the ceiling using the fixings provided. 

 

Secure the smoke alarm unit to the ceiling mounted base by aligning the mounting slots around the base and turning a half click. 

 

Once the base clicks into the base plate the smoke alarm is now secure and mounted correctly. 

Press the TEST button to check it is functioning correctly AFTER installation.

 

 

6.Testing your Interlinked Smoke Alarm  

WARNING!

Test each smoke alarm to ensure it has been installed correctly and is operating properly.

The TEST button can be used to test all functions of the alarm. 

 

We recommend you test the alarm weekly. To test, press the TEST button for 2 seconds and the smoke alarm will emit an audible alarm. Release the TEST button and the audible alarm will stop. This completes the weekly testing procedure. 

If the smoke alarm fails to emit an audible alarm when the TEST button is pressed, the smoke alarm should be replaced with a smoke alarm that operates correctly. 

If the smoke alarm emits an audible alarm when the alarm is not being tested, this could indicate the presence of fire and should be investigated by the user.

 

7.Maintenance and Cleaning 

The smoke alarm has been designed to be as maintenance free as possible. To ensure the continued operation of the smoke alarm you should; 

Test the smoke alarm once per week

Clean the smoke alarm intakes once per month gently using a vacuum head attachment – NEVER use cleaning agents, liquids or solvents and they may damage the unit and invalidate the manufacturer’s warranty. 

If the smoke alarm has a low battery condition, the alarm will emit and audible beep once every 50 seconds and the LED will flash indicating low battery. In the event of low battery condition, the smoke alarm should be replaced as the alarm has reached the end of its life and will no longer offer detection protection or early warning of fire.

 

8.Fire Safety Best Practice

If the smoke alarm emits an audible alert/sound it is indicating that a possible fire condition has been detected. It is recommended that all persons at home, where the smoke alarm is to be installed, is made aware of the location, sound, and operation of the smoke alarm. 

It is also recommended that all households have a fire escape plan in place and have considered what actions to take in the event of a fire in the home to ensure all occupants can reach a place of safety.

 

9.What to do in the Event of Fire

Leave the room or area as quickly as possible to reach a place of safety. Follow the buildings fire escape plan. Ensure the fire service/department have been called. 

Do not enter the room, area or building until the fire service/department have instructed you to do so

 

10.Trouble Shooting

If the LED flashes and the smoke alarm emits an audible alert/sound every 50 seconds, this indicates low battery condition and the smoke alarm should be replaced. 

If the smoke alarm sounds unwanted, false alarms the smoke alarm is more than likely installed in the wrong location and either steam, cooking fumes, insects etc are causing unwanted, false alarms.

In this case the smoke alarm should be located properly in accordance with Section 3. Where to Install your Interlinked Smoke Alarm. 

 

11. Limitations of Smoke Alarms

There is a statistical correlation between lower fire deaths in the home and an increased level of smoke alarm ownership across the world. However, like any safety device, smoke alarms can only provide a suitable level of protection if they are designed, installed, and maintained correctly.

Smoke alarms may not alert all individuals of a fire condition in instances where the persons suffer from a hearing impairment or are under the influence of drugs and/or alcohol. It is recommended that once smoke alarms are installed, ALL persons in the home can hear the alarm.   

Photoelectric smoke alarms may not provide early warning of fire where the combustion efficiency is high thus flaming combustion is present with little or no smoke or where an accelerant has been used. 

Consideration should be given by the homeowner to the type of smoke alarm to be installed and the relevance to the risk/type of fire expected in the home.  

If low battery condition is detected OR the smoke alarm is more than 10 years old the smoke alarm should be replaced in both cases

 

12.Limited Warranty 

We warrant solely to the original consumer/purchaser of each new Interlinked Smoke Alarm that the product shall be free from defects in material and workmanship under normal use, and conditional upon the manufacturer’s maintenance advice being met, for a period of 3 years from the date of purchase. This warranty DOES NOT cover damage resulting from accident or misuse or abuse or lack of reasonable care for the product. 

The manufacturer can never be made liable for loss and/or damage of whatever nature, including incidental and/or consequential loss arising from the fact that the signal from the smoke alarm did not sound during smoke or fire because of flat or faulty batteries (in circumstances where battery installation and maintenance is completely outside of the manufacturer’s control).   

Firexo Limited, ℅ CWD, Boughton Business Park, Bell Lane, Amersham, Buckinghamshire, HP6 6FAwww.firexo.comFIREXO S.R.L., Foro Buonaparte, 12, 20121 Milano, Italy